Electrical / Calculator

Reactive Compensation Estimate

Estimate capacitor reactive power for improving an inductive load’s power factor.

Calculator

Reactive Compensation Estimate

Change the inputs to match your equipment. Results update automatically.

Calculated result -

Formula

Qc = P(kW) x (tan phi1 - tan phi2)

Worked example

For 100 kW, improving power factor from 0.80 to 0.95 gives Qc = 100 × (tan(arccos 0.80) − tan(arccos 0.95)) ≈ 42.13 kVAr.

Scope and interpretation

Check harmonics, resonance, switching steps and the actual load profile before capacitor selection.